CALCULATION OF REACTIVE POWER
lag. Calculate the leading kVAr necessary to correct the power factor to 0.95 lag. If the
transformer has a rated conductor loss equal to 1% of the transformer rating, calculate
the energy saved assuming 24-hour operation at the operating load.
Given Data:
•Transformer capacity (rated) = 5 MVA
•Transformer actual loading = 4.5 MVA
•Load power factor = 0.82 lagging
•Rated transformer loss = 1% of transformer rating
•Operating hours = 24
•CosØ1 = 0.82 lagging
•CosØ2 = 0.95 lagging
Task:
•Required leading kVAr to correct power factor at 0.95 lagging
Calculations:
𝐸𝑥𝑖𝑠𝑡𝑖𝑛𝑔 𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟 𝑎𝑛𝑔𝑙𝑒 = ∅1 = cos−1 0.82 = 34.9°
𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟 𝑎𝑛𝑔𝑙𝑒 = ∅2 = cos−1 0.95 = 18.2°
𝑃 = 𝑆1 cos ∅1 = 4.5 × 0.82 = 3.69 𝑀𝑊
𝑄1 = 𝑆1 sin ∅1 = 4.5 × 0.572 = 2.574 𝑀𝑉𝐴𝑟
𝑄2 = 𝑃 tan ∅2 = 3.69 × tan 18.2 = 1.214 𝑀𝑉𝐴𝑟
The leading MVAr necessary to improve the power factor from 0.82 to 0.95
= Q1-Q2 = 1.362 MVAr
For a transformer load with improved power factor,
If you any query contact us through mail or whatsapp.
Post a Comment
Please do not enter any spam link in the come box.